AquaForce® 30XW High-Efficiency, Water-Cooled Indoor Liquid Screw Chil
AquaForce® 30XW High-Efficiency, Water-Cooled Indoor Liquid Screw Chiller R-134a Refrigerant
AquaForce® 30XW High-Efficiency, Water-Cooled Indoor Liquid Screw Chiller R-134a Refrigerant
Online Quotation
Online Quotation
This product requires a custom quote to ensure it meets your specific needs. Call us now to discuss your requirements and receive a personalized quote from our friendly sales team!
- Description
- Additional Details
The 30XW units are high-efficiency, indoor water-cooled chillers with a quiet, low-vibration design featuring screw compressors. The units have excellent part load efficiency and a compact footprint less than 48 in. wide, making them great replacement units.
Performance Features
- AHRI certified efficiencies to 0.468 kW per ton IPLV
- Chlorine-free R-134a HFC refrigerant
- Low energy consumption during part load and full load operation
- Available operational voltages include: 200-v, 230-v, 380-v, 460-v, 575-v (60 Hz)
- Wye-delta starter is standard on 200-v and 230-v units (factory-installed option for all other units)
- Leaving-fluid temperature directly controlled to within 0.5°F (0.3°C)
- Entering-fluid temperature continuously monitored to detect flow or load changes
- Compatible with Carrier Comfort Network® (CCN) communication link
- ASHRAE 90.1 compliant
- Certified in accordance with AHRI Standard 550/590
- Heat recovery capability up to 140°F (60°C)
Reliability Features
- Dual independent refrigeration circuits (sizes 325-400)
- Low voltage control circuits
- Short cycle protection
- Dual chiller control
- Temperature reset from return fluid
- Chilled water flow switch
- Electronic refrigerant gauges
- Listed with UL and UL, Canada
Maintenance Features
- Hermetic twin screw compressors
- Mechanically cleanable condenser and evaporator
- Alarm contacts
- Filter drier
- Moisture indicating sight glass
- Accessible service information including suction and discharge pressure and temperature using Navigator™ display module (factory-installed option or field-installed accessory)
- ON/OFF control switch
Installation Features
- Unit width of 48 in. or less
- Single point electrical connection (with optional control power transformer)
- Heat mode controls standard
Standard Warranty
- One year parts only
- Extended warranties available
Factory-Installed Options
- Wye-delta start
- Dual point power connection (325-400 ton)
- Non-fused disconnect
- Control power transformer
- 115-v GFCI (ground fault circuit interrupter) convenience outlet
- Marine water boxes
- Flange connections
- Suction service valves
- Isolation valves
- One-pass evaporator water box
- Three-pass evaporator water box
- 300 psi (2068 kPA) water side operating pressure rating
- One-pass condenser water box
- Minimum load control
- Navigator display module
- LON (Local Operating Network) translator control
- BACnet Communication
- EMM (Energy Management Module)
- Standard water-side operating pressure of 150 psig (1034 kPa) with an available option of 300 psig (2068 kPa)
- Discharge and liquid line shutoff valves
Field-Installed Accessories
- Temperature reset sensor
- EMM
- LON translator control
- BACnet translator control
- Sound Attenuation Packages
- Navigator display module
- Neoprene vibration isolation pads
- Vibration isolation springs
Physical Data
Size | Capacity | Input power (kW) |
Evaporator flow |
Evaporator pressure drop |
Condenser flow | Condenser pressure drop |
|||||
---|---|---|---|---|---|---|---|---|---|---|---|
tons | output (kW) | gpm | L/s | Ft of water |
kPa | gpm | L/s | Ft of water |
kPa | ||
150 | 160.0 | 562.7 | 105.0 | 384 | 24.2 | 11.1 | 33.2 | 480 | 30.3 | 14.1 | 42.1 |
175 | 170.1 | 598.2 | 110.5 | 408 | 25.8 | 12.4 | 37.1 | 510 | 32.2 | 15.8 | 47.2 |
185 | 178.2 | 626.7 | 120.1 | 428 | 27.0 | 13.6 | 40.7 | 535 | 33.7 | 17.2 | 51.4 |
200 | 191.1 | 672.1 | 123.9 | 459 | 28.9 | 15.4 | 46.0 | 573 | 36.2 | 19.5 | 58.3 |
225 | 222.5 | 782.5 | 147.7 | 534 | 33.7 | 12.0 | 35.9 | 668 | 42.1 | 12.8 | 38.3 |
250 | 241.1 | 847.9 | 151.9 | 579 | 36.5 | 13.9 | 41.5 | 723 | 45.6 | 14.9 | 44.5 |
260 | 244.8 | 861.0 | 165.7 | 588 | 37.1 | 14.3 | 42.7 | 734 | 46.3 | 15.3 | 45.7 |
275 | 262.8 | 924.3 | 168.2 | 631 | 39.8 | 16.3 | 48.7 | 788 | 49.7 | 17.4 | 52.0 |
300 | 285.5 | 1004.1 | 184.3 | 685 | 43.2 | 18.9 | 56.5 | 857 | 54.0 | 20.3 | 60.7 |
325 | 322.2 | 1133.0 | 204.7 | 773 | 48.8 | 15.6 | 46.6 | 966 | 61.0 | 10.9 | 32.6 |
350 | 343.0 | 1206.3 | 216.8 | 823 | 51.9 | 17.4 | 52.0 | 1029 | 64.9 | 12.3 | 36.8 |
375 | 364.3 | 1281.2 | 236.5 | 874 | 55.2 | 19.5 | 58.3 | 1093 | 69.0 | 13.7 | 41.0 |
400 | 385.0 | 1354.0 | 242.8 | 924 | 58.3 | 21.5 | 64.3 | 1155 | 72.9 | 15.2 | 45.4 |
Size | Full load efficiency (kW/Ton) |
IPLV (kw/Ton) |
---|---|---|
150 | 0.656 | 0.561 |
175 | 0.650 | 0.550 |
185 | 0.674 | 0.563 |
200 | 0.648 | 0.556 |
225 | 0.664 | 0.537 |
250 | 0.630 | 0.526 |
260 | 0.677 | 0.547 |
275 | 0.640 | 0.534 |
300 | 0.646 | 0.539 |
325 | 0.636 | 0.476 |
350 | 0.632 | 0.472 |
375 | 0.649 | 0.481 |
400 | 0.631 | 0.475 |
LEGEND
AHRI = Air Conditioning, Heating and Refrigeration Institute
IPLV = Integrated Part Load Value
NOTES
1. Rated in accordance with AHRI Standard 550/590 at standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving Water Temperature: 44°F (6.7°C)
Flow: 2.4gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering Water Temperature: 85°F (29.4°C)
Flow: 3.0gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler):
0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)
- IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions.
- All data in the above table was generated in Packaged Chiller Builder version 3.29. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
- Contact Carrier for custom ratings.