AquaForce® 30HX High-Efficiency Indoor Liquid Screw Chiller
AquaForce® 30HX High-Efficiency Indoor Liquid Screw Chiller
AquaForce® 30HX High-Efficiency Indoor Liquid Screw Chiller
Online Quotation
Online Quotation
This product requires a custom quote to ensure it meets your specific needs. Call us now to discuss your requirements and receive a personalized quote from our friendly sales team!
- Description
- Additional Details
High-Efficiency Indoor Liquid Screw Chiller
30HXA - Condenser less
30HXC - Water-Cooled
The 30HX units are high-efficiency, indoor water-cooled or condenser less chillers. The units have a quiet, low-vibration design featuring screw compressors. The 30HX chillers are compact enough to fit through a standard door, making them great replacement units.
Performance Features
- Chlorine-free HFC-134a refrigerant
- Low energy consumption during part load and full load operation
- 208/230 v, 230 v, 460 v, 575 v operational voltages available
- Wye-delta start is standard on 208/230 v and 230 v 50/60 Hz units (factory-installed option for all other units)
- Leaving-fluid temperature directly controlled to within 0.5°F (0.3°C)
- Entering-fluid temperature continuously monitored to detect flow or load changes
- Compatible with Carrier Comfort Network® (CCN) communication link
- Heat recovery capability up to 135°F (57.22°C)
Reliability Features
- Low voltage control circuits
- Short cycle protection
- Dual chiller control
- Temperature reset from return fluid
- Chilled water flow switch
- Electronic refrigerant gauges
Maintenance Features
- Hermetic twin screw compressors
- Mechanically cleanable condenser and cooler (30HXC)
- Alarm contacts
- Filter drier
- Moisture indicating sight glass
- Accessible service information including suction and discharge pressure and temperature using Navigator™ display module
- Discharge and liquid line shutoff valves
- ON/OFF control switch
Installation Features
- Modular construction
- Fits through standard doorway
- Single point electrical connection
- Easy connections for remote condensers (30HXA)
- Heat mode controls as standard
Standard Warranty
- One year from start-up or 18 months from shipment
- Extended warranty
Factory-Installed Options
- Wye-delta start
- Brine
- Minus-one-pass cooler head
- Plus-one-pass cooler head
- Minimum load control
- Suction service valves
- EMM (Energy Management Module)
Field-Installed Options
- Chilled water flow switch
- Thermistor
- Control power transformer
- Remote enhanced display
- Minimum load control
- Chillervisor™
- Outside temperature reset sensor
- EMM (Energy management module)
- BACnet translator
- LONWorks translator
Field-Installed Accessories
- Neoprene vibration isolators (field-installed accessory)
- Control power transformer
- Minimum load control
- Sound reduction enclosure
- Vibration isolation
- Temperature reset sensor
- Chillervisor™ System Manager III
- Cooler head insulation
- EMM (Energy Management Module)
- Sesimic compliance option
Physical Data
Capacity | Input power (kW) |
Cooler flow |
Cooler pressure drop |
Condenser flow |
Condenser pressure drop |
||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Tons | Output (kW) | gpm | L/s | Ft of Water |
kPa | gpm | L/s | Ft of Water |
kPa | ||
076 | 75.4 | 265.2 | 53.7 | 181.0 | 11.4 | 14.5 | 43.2 | 226.2 | 14.3 | 8.9 | 26.6 |
086 | 83.0 | 292.3 | 60.4 | 199.3 | 12.6 | 17.2 | 51.4 | 249.1 | 15.7 | 10.7 | 31.8 |
096 | 94.0 | 330.5 | 67.0 | 225.5 | 14.2 | 17.0 | 50.7 | 281.9 | 17.8 | 10.9 | 32.7 |
106 | 104.3 | 366.8 | 75.3 | 250.4 | 15.8 | 15.4 | 46.0 | 313.0 | 19.7 | 13.3 | 39.6 |
116 | 113.5 | 399.3 | 83.2 | 272.3 | 17.2 | 13.3 | 39.8 | 340.4 | 21.5 | 17.0 | 50.6 |
126 | 122.9 | 432.1 | 92.2 | 294.9 | 18.6 | 15.4 | 45.9 | 368.6 | 23.3 | 19.6 | 58.5 |
136 | 136.5 | 479.9 | 97.0 | 327.5 | 20.7 | 14.6 | 43.7 | 409.4 | 25.8 | 18.5 | 55.1 |
146 | 145.6 | 513.2 | 105.1 | 350.2 | 22.1 | 16.5 | 49.3 | 437.8 | 27.6 | 20.9 | 62.4 |
161 | 156.6 | 550.6 | 111.6 | 375.7 | 23.7 | 13.7 | 40.9 | 469.7 | 29.6 | 21.3 | 63.6 |
171 | 165.92 | 585.3 | 118.3 | 398.0 | 25.1 | 15.2 | 45.4 | 497.6 | 31.4 | 17.2 | 51.4 |
186 | 177.1 | 623.1 | 126.7 | 425.1 | 26.8 | 13.9 | 41.5 | 531.4 | 33.5 | 19.5 | 58.1 |
206 | 211.6 | 744.0 | 146.4 | 507.7 | 32.0 | 14.7 | 43.9 | 634.7 | 40.0 | 20.9 | 62.4 |
246 | 248.6 | 874.1 | 172.4 | 596.5 | 37.6 | 16.2 | 48.3 | 745.7 | 47.0 | 21.9 | 65.2 |
261 | 257.2 | 904.6 | 180.4 | 617.2 | 38.9 | 17.2 | 51.4 | 771.5 | 48.7 | 23.3 | 69.5 |
271 | 267.4 | 940.3 | 189.5 | 641.7 | 40.5 | 18.5 | 55.1 | 802.2 | 50.6 | 25.1 | 74.7 |
Size | Full load efficiency (kW/Ton) |
IPLV† (kw/Ton) |
---|---|---|
076 | 0.712 | 0.512 |
086 | 0.728 | .0523 |
096 | 0.714 | 0.513 |
106 | 0.722 | 0.520 |
116 | 0.733 | 0.530 |
126 | 0.750 | 0.541 |
136 | 0.711 | 0.527 |
146 | 0.720 | 0.534 |
161 | 0.713 | 0.521 |
171 | 0.713 | 0.539 |
186 | 0.715 | 0.561 |
206 | 0.692 | 0.511 |
246 | 0.693 | 0.525 |
261 | 0.702 | 0.525 |
271 | 0.709 | 0.527 |
LEGEND
IPLV = Integrated Part Load Value
†IPLV shown is the lower of Sequence A or Sequence B unloading.
- NOTES
1. Rated (60Hz unit) in accordance with AHRI Standard 550/590 at standard rating conditions.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving Water Temperature: 44°F (6.7°C)
Flow: 2.4gpm per ton (0.043 L/s per kW)
Condenser Conditions:
Entering Water Temperature: 85°F (29.4°C)
Flow: 3.0gpm per ton (0.054 L/s per kW)
Fouling Factor (Cooler):
0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)
Fouling Factor (Condenser):
0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)
- IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions
- All data in the above table was generated in Packaged Chiller Builder version 3.47. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
- Contact Carrier for custom ratings.