High-Efficiency Indoor Liquid Screw Chiller
30HXA - Condenser less
30HXC - Water-Cooled

The 30HX units are high-efficiency, indoor water-cooled or condenser less chillers. The units have a quiet, low-vibration design featuring screw compressors. The 30HX chillers are compact enough to fit through a standard door, making them great replacement units.

Performance Features

  • Chlorine-free HFC-134a refrigerant
  • Low energy consumption during part load and full load operation
  • 208/230 v, 230 v, 460 v, 575 v operational voltages available
  • Wye-delta start is standard on 208/230 v and 230 v 50/60 Hz units (factory-installed option for all other units)
  • Leaving-fluid temperature directly controlled to within 0.5°F (0.3°C)
  • Entering-fluid temperature continuously monitored to detect flow or load changes
  • Compatible with Carrier Comfort Network® (CCN) communication link
  • Heat recovery capability up to 135°F (57.22°C)

Reliability Features

  • Low voltage control circuits
  • Short cycle protection
  • Dual chiller control
  • Temperature reset from return fluid
  • Chilled water flow switch
  • Electronic refrigerant gauges

Maintenance Features

  • Hermetic twin screw compressors
  • Mechanically cleanable condenser and cooler (30HXC)
  • Alarm contacts
  • Filter drier
  • Moisture indicating sight glass
  • Accessible service information including suction and discharge pressure and temperature using Navigator™ display module
  • Discharge and liquid line shutoff valves
  • ON/OFF control switch

Installation Features

  • Modular construction
  • Fits through standard doorway
  • Single point electrical connection
  • Easy connections for remote condensers (30HXA)
  • Heat mode controls as standard

Standard Warranty

  • One year from start-up or 18 months from shipment
  • Extended warranty

Factory-Installed Options

  • Wye-delta start
  • Brine
  • Minus-one-pass cooler head
  • Plus-one-pass cooler head
  • Minimum load control
  • Suction service valves
  • EMM (Energy Management Module)

Field-Installed Options

  • Chilled water flow switch
  • Thermistor
  • Control power transformer
  • Remote enhanced display
  • Minimum load control
  • Chillervisor™
  • Outside temperature reset sensor
  • EMM (Energy management module)
  • BACnet translator
  • LONWorks translator

Field-Installed Accessories

  • Neoprene vibration isolators (field-installed accessory)
  • Control power transformer
  • Minimum load control
  • Sound reduction enclosure
  • Vibration isolation
  • Temperature reset sensor
  • Chillervisor™ System Manager III
  • Cooler head insulation
  • EMM (Energy Management Module)
  • Sesimic compliance option

Physical Data

Capacity Input
power
(kW)
Cooler
flow
Cooler
pressure
drop
Condenser
flow
Condenser
pressure
drop
Tons Output (kW) gpm L/s Ft of
Water
kPa gpm L/s Ft of
Water
kPa
076 75.4 265.2 53.7 181.0 11.4 14.5 43.2 226.2 14.3 8.9 26.6
086 83.0 292.3 60.4 199.3 12.6 17.2 51.4 249.1 15.7 10.7 31.8
096 94.0 330.5 67.0 225.5 14.2 17.0 50.7 281.9 17.8 10.9 32.7
106 104.3 366.8 75.3 250.4 15.8 15.4 46.0 313.0 19.7 13.3 39.6
116 113.5 399.3 83.2 272.3 17.2 13.3 39.8 340.4 21.5 17.0 50.6
126 122.9 432.1 92.2 294.9 18.6 15.4 45.9 368.6 23.3 19.6 58.5
136 136.5 479.9 97.0 327.5 20.7 14.6 43.7 409.4 25.8 18.5 55.1
146 145.6 513.2 105.1 350.2 22.1 16.5 49.3 437.8 27.6 20.9 62.4
161 156.6 550.6 111.6 375.7 23.7 13.7 40.9 469.7 29.6 21.3 63.6
171 165.92 585.3 118.3 398.0 25.1 15.2 45.4 497.6 31.4 17.2 51.4
186 177.1 623.1 126.7 425.1 26.8 13.9 41.5 531.4 33.5 19.5 58.1
206 211.6 744.0 146.4 507.7 32.0 14.7 43.9 634.7 40.0 20.9 62.4
246 248.6 874.1 172.4 596.5 37.6 16.2 48.3 745.7 47.0 21.9 65.2
261 257.2 904.6 180.4 617.2 38.9 17.2 51.4 771.5 48.7 23.3 69.5
271 267.4 940.3 189.5 641.7 40.5 18.5 55.1 802.2 50.6 25.1 74.7

 

Size Full load
efficiency
(kW/Ton)
IPLV†
(kw/Ton)
076 0.712 0.512
086 0.728 .0523
096 0.714 0.513
106 0.722 0.520
116 0.733 0.530
126 0.750 0.541
136 0.711 0.527
146 0.720 0.534
161 0.713 0.521
171 0.713 0.539
186 0.715 0.561
206 0.692 0.511
246 0.693 0.525
261 0.702 0.525
271 0.709 0.527

LEGEND

IPLV = Integrated Part Load Value
†IPLV shown is the lower of Sequence A or Sequence B unloading.

  1. NOTES
    1. Rated (60Hz unit) in accordance with AHRI Standard 550/590 at standard rating conditions.
    2. Standard rating conditions are as follows:

    Cooler Conditions:
    Leaving Water Temperature: 44°F (6.7°C)
    Flow: 2.4gpm per ton (0.043 L/s per kW)

    Condenser Conditions:
    Entering Water Temperature: 85°F (29.4°C)
    Flow: 3.0gpm per ton (0.054 L/s per kW)

    Fouling Factor (Cooler):
    0.00010 hr x sq ft x °F per Btuh (0.000018m2 x K per W)

    Fouling Factor (Condenser):
    0.00025 hr x sq ft x °F per Btuh (0.000044m2 x K per W)
  •  IPLV is a single number part load efficiency value calculated from using the efficiency values at 100%, 75%, 50%, and 25% of load when the chiller is operating in AHRI conditions
  • All data in the above table was generated in Packaged Chiller Builder version 3.47. Please refer to the most current version of the Packaged Chiller Builder for the most up-to-date data.
  •  Contact Carrier for custom ratings.